HRV/ERV Solutions VS900 CMe
- Download :
- Catalog
Dimensions
Parts
Feature
PERFORMANCE
Exceptional energy performance thanks to its aluminum counterflow heat exchanging core.
Significant cost of operation savings.
Quiet operation with fans that use electronically commutated motors (ECM) and backward curving fan blades.
FAN OPERATING RANGE
FAN VOLUME & POWER RANGE
Ext. Static Pressure(in. W.C.) (in. W.C.) |
0.34 | 1.20 | 1.83 | 2.28 | 2.61 |
---|---|---|---|---|---|
Maximum Flow (CFM) | 900 | 700 | 500 | 300 | 100 |
System Power (Watts) | 797 | 882 | 786 | 640 | 429 |
Scroll
LATENT EFFICIENCY
SENSIBLE EFFICIENCY
TOTAL EFFICIENCY
Specifications
Ventilation Flow – Max | 992 cfm |
---|---|
Ventilation Flow – Typical | 200 to 900 cfm |
Ventilation Type | Energy Recovery Ventilator (ERV) |
Heat Exchanger | Counterflow Polymer Static Plate |
Fan Type | Backward Curved, Centrifugal, EC |
Heat Recovery – Max | 79.2% |
Temperature Range | 41° F to 104° F |
Humidity | 90% RH |
Operation Modes | CAV, DCV, VAV, BMS, Economizer |
MECHANICAL
Weight | 375 lbs |
---|---|
Shipping Weight | 550 lbs |
Dimensions | 54.53" L x 15.35" W x 66.93" H |
Shipping Dimensions | 64" L x 26" W x 77" H |
OA Filter Dimensions | 23" x 12.25" W x 3.75" D Filter Class: MERV13 |
RA Filter Dimensions | 23" x 12.25" W x 3.75" D Filter Class: MERV9 |
ELECTRICAL
*Preheater | Inactive | Inactive | Active | Active |
---|---|---|---|---|
Voltage | 240 VAC | 208 VAC | 240 VAC | 208 VAC |
Phase | 1Φ | 1Φ | 1Φ | 1Φ |
Power Supply | 960 W | 960 W | 6.26 kW | 4.95 kW |
FLA – Max | 4 A | 4.6 A | 26.1 A | 23.8 A |
MCA | 4.4 A | 5.1 A | 32 A | 29.1 A |
MOP | 10 A | 10 A | 35 A | 30 A |
De-Ice Preheater | – | – | 5.3 kW | 3.99 kW |
Preheater Temp Rise | – | – | 10.5° C | 7.9° C |
Fan Motor Type | EC | |||
Maximum Power – 1 Fan | 470 W (0.63 hp) |
- *
- Preheater recommended for below-freezing outdoor temperatures.