HRV/ERV Solutions VS500 SQ

- Download :
-
Catalog
Dimensions

Parts

Feature
SOUND PERFORMANCE
FROM EXHAUST AIR DUCT
Sound Power Per Frequency Band (Hz) | Overall | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
Fan Speed | CFM | 63 | 125 | 250 | 500 | 1k | 2k | 4k | 8k | LWA [dB] |
25% | 180 | 32.0 | 38.9 | 37.6 | 31.4 | 26.9 | 25.3 | 23.8 | 23.4 | 42.4 |
50% | 307 | 39.7 | 48.2 | 53.0 | 44.3 | 42.4 | 45.4 | 37.9 | 35.6 | 55.6 |
75% | 464 | 46.6 | 55.5 | 63.9 | 54.3 | 53.3 | 58.7 | 50.0 | 47.5 | 66.2 |
Boost | 539 | 49.2 | 56.9 | 64.2 | 56.0 | 53.4 | 57.2 | 54.3 | 53.8 | 66.8 |
Scroll
RADIATED FROM CASE
Sound Power Per Frequency Band (Hz) | Overall | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Fan Speed | CFM | 63 | 125 | 250 | 500 | 1k | 2k | 4k | 8k | LWA [dB] | LPA [dB]1 | LPA [dB]2 |
25% | 180 | 20.0 | 38.0 | 46.6 | 28.3 | 22.4 | 21.9 | 28.1 | 27.0 | 47.3 | 32.6 | 24.7 |
50% | 307 | 34.5 | 41.1 | 43.2 | 33.3 | 31.9 | 29.6 | 27.4 | 25.9 | 46.2 | 31.5 | 23.6 |
75% | 464 | 40.5 | 44.1 | 48.7 | 41.5 | 40.0 | 37.5 | 29.8 | 26.6 | 51.5 | 36.8 | 28.9 |
Boost | 539 | 44.4 | 48.4 | 51.0 | 46.5 | 44.9 | 42.4 | 34.2 | 27.9 | 55.0 | 40.3 | 32.4 |
Scroll
- 1
- Sound pressure levels calculated at 1 meter for Q = 4
- 2
- Sound pressure levels calculated at 3 meters for Q = 4
PERFORMANCE

Exceptional energy efficiency performance puts the VS500 SQ in a class by itself.

With its aluminum counterflow heat exchanger core, the VS500 SQ transfers 81% to 90% of the heat between fresh and exhaust air streams.

Our fans incorporate electronically commutated motors (ECMs) and backward curving fan blades, reducing the power required for air movement.
SPECIFIC FAN POWER

HEAT RECOVERY EFFICIENCY

EXAMPLE CLASSROOM AIR FLOW

ACCESSORIES
- PIR Presence Sensor
- Room CO2 Sensor
- Room RH Sensor
- VOC Sensor
- Smart Building Gateway
Specifications
Ventilation Flow – Max | 539 cfm |
---|---|
Ventilation Flow – Typical | 117 to 500 cfm |
Ventilation Type | Heat Recovery Ventilator (HRV) |
Heat Exchanger | Counterflow Aluminum Static Plate |
Fan Type | Backward Curved, Centrifugal, EC |
Heat Recovery – Max | 90% |
Temperature Range | 40° F to 104° F |
Humidity – Inside Max | 90% RH |
Operation Modes | CAV, DCV, Economizer |
Noise | 31 – 40 dBA |
Duct Connection (Room Air, Supply Air) |
None |
Duct Connection (Outside Air, Exhaust Air) |
12.4" Dia. (121 in2) Min. |
Temperature Control | Continuously Variable Bypass |
MECHANICAL
Weight | 280 lbs |
---|---|
Shipping Weight | 424 lbs |
Dimensions | 84.3" L x 44.0" W x 17.9" H |
Shipping Dimensions | 92" L x 60" W x 29" H |
OA Filter (Actual Size) | 18.9" x 19.7" W x 3.8" MERV13 |
RA Filter (Actual Size) | 10.6" L x 16.7" MERV8 |
Mounting Dimension | 30.1" x 82.9" |
External Finish | Powder Coat Over Aluminum |
ELECTRICAL
Power Supply | 2.34 kW |
---|---|
Voltage | 240 VAC 1Φ, 60Hz |
FLA – Max | 11.4 A, 1Φ |
De-Ice Preheater | 3.0 kW |
Fan Motor Type | EC |
Maximum Power – 1 Fan | 170W (.23hp) |