HRV/ERV Solutions VS400 CMh

Download :
Catalog

Dimensions

Parts

Feature

PERFORMANCE

Exceptional energy performance thanks to its aluminum counterflow heat exchanging core.

Significant cost of operation savings.

Quiet operation with fans that use electronically commutated motors (ECM) and backward curving fan blades.

HEAT RECOVERY EFFICIENCY

FAN OPERATING RANGE

FAN VOLUME

Ext. Static Pressure
(in. W.C.)
0.52 1.27 2.01 2.70
Maximum Flow (CFM) 400 300 200 100
System Power (Watts) 815 390 389 357
Scroll

FAN POWER*

Airflow (CFM) 450 400 300 200 100
CFM/WATT (2 Fans) 1.3 1.5 2.1 2.6 2.7
System Power (Watts) 361 282 166 96 57
Scroll
*
At 1/8" water column

Specifications

Ventilation Flow – Max 467 cfm
Ventilation Flow – Typical 120 to 480 cfm
Ventilation Type Heat Recovery Ventilator (HRV)
Heat Exchanger Counterflow Aluminum Static Plate
Fan Type Backward Curved, Centrifugal, EC
Heat Recovery – Max 86.1%
Temperature Range 41° F to 104° F
Humidity 90% RH
Operation Modes CAV, DCV, VAV, BMS, Economizer

MECHANICAL

Weight 198 lbs
Shipping Weight 254 lbs
Dimensions 42.52" L x 12.2" W x 55.12" H
Shipping Dimensions 51" L x 18" W x 67" H
OA Filter Dimensions 18" x 9.25" W x 3.75" D Filter Class: MERV13
RA Filter Dimensions 18" x 9.25" W x 3.75" D Filter Class: MERV9

ELECTRICAL

*Preheater Inactive Inactive Active Active
Voltage 240 VAC 208 VAC 240 VAC 208 VAC
Phase
Power Supply 360 W 360 W 3.29 kW 2.57 kW
FLA – Max 1.5 A 1.7 A 13.7 A 12.2 A
MCA 1.6 A 1.8 A 16.8 A 15.1 A
MOP 5 A 5 A 20 A 15 A
De-Ice Preheater 2.93 kW 2.21 kW
Preheater Temp Rise 12.5° C 9.4° C
Fan Motor Type EC
Maximum Power – 1 Fan 170 W (0.23 hp)
*
Preheater recommended for below-freezing outdoor temperatures.