Heat Pump Type V-II Series AOUA96RLCV  [3Phase]

Outdoor unit

Outdoor Unit :
AOUA96RLCV
Download :
Catalog

Features

  • Operational efficiency
  • Energy saving technology

Capacity

Cooling  96,000 BTU/h
Heating  108,000 BTU/h


Specification

Rating Capacity Range 8
Maximum Connectable Indoor Unit 16
Scroll
Power source Phase 3-phase
Voltage 460 V
Frequency 60 Hz
Capacity Cooling 96,000 BTU/h
28.1 kW
Heating 108,000 BTU/h
31.7 kW
Input Power Cooling 7.67 kW
Heating 7.90 kW
EER (Non-Ducted/Ducted) Cooling 11.7 / 11.3 Btu/hW
IEER (Non-Ducted/Ducted) Cooling 23.6 / 20.2 Btu/hW
COP (Non-Ducted/Ducted) Heating 3.72 / 3.60 W/W
Air Flow Rate 6,533 CFM (11,100 m³/h)
Sound Pressure Level Cooling 59 dB(A)
Heating 59 dB(A)
Maximum external static pressure 0.32 in.WG (80 Pa)
Compressor motor output 7.5 kW
Net Dimensions Height 66-9/16 inch (1,690 mm)
Width 36-5/8 inch (930 mm)
Depth 30-1/8 inch (765 mm)
Net Weight 584 lbs (265 kg)
Refrigerant Type R410A
Charge 25.79 lbs (11.70 kg)
Connection Pipe Diameter Liquid 1/2 inch (12.70 mm)
Discharge Gas 7/8 inch (22.22 mm)
Operation Range Cooling 5 to 115 °FDB (-15 to 46 °CDB)
Heating -4 to 70 °FDB (-20 to 21 °CDB)
Scroll
Note :
Specifications are based on the following conditions.
Cooling :
Indoor temperature of 80°F (26.7°C) DB / 67°F (19.4°C) WB, and outdoor temperature of 95°F (35.0°C) DB / 75°F (23.9°C) WB.
Heating :
Indoor temperature of 70°F (21.1°C) DB / 60°F (15.6°C) WB, and outdoor temperature of 47°F (8.3°C) DB / 43°F (6.1°C) WB.
Pipe length :
25ft. (7.5 m); Height difference between outdoor unit and indoor unit : 0ft. (0 m).
*1
Electrical data is only for outdoor unit.

Dimensions

Outdoor Unit : AOUA96RLCV

Outdoor unit