Heat Pump for Small Capacity Type J-IVS Series AOU36RLAVS4

Outdoor unit

Outdoor Unit :
AOU36RLAVS4
Download :
Catalogues

Features

  • Compact design *
  • Up to 12 indoor units can be connected (4Ton) *
  • Long piping length *


Specification

Rating Capacity Range 3 Ton HP
Scroll
Power source Phase Single-phase 1
Voltage 208/230 V
Frequency 60 Hz
Air Flow Rate 2,472 CFM
4200 m³/h
Sound Pressure Level Cooling 52 dB(A)
Heating 54 dB(A)
Maximum external static pressure 0.10 in.WG
25 Pa
Compressor motor output 2.1 kW
Heat exchanger fin Blue fin
Net Dimensions Height 39- 5/16 inch
998 mm
Width 38- 3/16 inch
970 mm
Depth 14- 9/16 inch
370 mm
Net Weight 196 lbs
89 kg
Refrigerant Type R410A
Charge 8.82 lbs
4.0 kg
Connection Pipe Diameter Liquid φ3/8 inch
φ9.52 mm
Gas φ5/8 inch
φ15.88 mm
Total pipe length 262 ft.
80 m
Max. height difference
(Outdoor Unit: Upper/Lower)
98 / 98 ft.
30 / 30 m
Operation Range Cooling 23 to 115 °FDB
-5 to 46 °CDB
Heating -15 to 70 °FDB
-26 to 21 °CDB
Scroll
*
There is no change from the conventional model.
Note :
Specifications are based on the following conditions.
Cooling:
Indoor temperature of 80°F (26.7°C) DB / 67°F (19.4°C) WB, and outdoor temperature of 95°F (35.0°C) DB / 75°F (23.9°C) WB.
Heating:
Indoor temperature of 70°F (21.1°C) DB / 60°F (15.6°C) WB, and outdoor temperature of 47°F (8.3°C) DB / 43°F (6.1°C) WB.
Pipe length:
25ft. (7.5 m); Height difference between outdoor unit and indoor unit : 0ft. (0 m).

Dimensions

Outdoor Unit : AOU36RLAVS4